Only qualified personnel should install this unit. Personnel should have a clear understanding of these instructions and should be aware of general saf
10Model LFC Low-Profile Fan Coil®Steam Coils, General - continued3. Standard steam coils are pitched in the casings when installed for horizontal air
11Model LFC Low-Profile Fan Coil®YearlyBearings — Most bearings are permanently lubricated and require no further lubrication under normal use. Normal
12Model LFC Low-Profile Fan Coil®Coil Maintenance Start-Up DocumentationCAUTIONFin edges are sharp.Coils must be clean to obtain maximum performance.
13Model LFC Low-Profile Fan Coil®Maintenance Log Date __________________ Time _____________ AM/PMNotes:_______________________________________________
14Model LFC Low-Profile Fan Coil®Maintenance Log Date __________________ Time _____________ AM/PMNotes:_______________________________________________
15Model LFC Low-Profile Fan Coil®Maintenance Log Date __________________ Time _____________ AM/PMNotes:_______________________________________________
16464496 • LFC, Rev. 1, August 2004 Copyright 2004 © Greenheck Fan CorporationGreenheck warrants this equipment to be free from defects in material a
2Model LFC Low-Profile Fan Coil®The unit should be stored at least 3½ in. (89 mm) off the floor on wooden blocks covered with moisture proof paper or p
3Model LFC Low-Profile Fan Coil®Table of ContentsInstallationUnit Layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3Lifting / Hang
4Model LFC Low-Profile Fan Coil®Unit DimensionsUnit SizeIJ K WidthInlet Outletw/o Filter w/ 2 in. Filter w/ 4 in. Filter Height Width Height Width15 4
5Model LFC Low-Profile Fan Coil®Coil DimensionsNOTEFluid enters the coil from the bottom connection (Inlet) and exits from the top (Outlet).Hot Water
6Model LFC Low-Profile Fan Coil®Unit SizeA B4 row 6 row 8 rowC D C D C D30 12.00 7.00 0.625 0.625 0.625 0.875 0.625 0.87545 12.00 7.00 0.625 0.625 0.6
7Model LFC Low-Profile Fan Coil®System Start-UpFor proper unit function and safety, follow everything in this start-up procedure in the order presente
8Model LFC Low-Profile Fan Coil®Symptom Possible Cause Corrective ActionBlower fails to operateBlown fuse or open circuit breaker Replace fuse or rese
9Model LFC Low-Profile Fan Coil®Hot Water, Chilled Water Coils1. Piping should be in accordance with accepted industry standards. Pipework should be